F800 And A800 Series (When Built-In Rs-485 Terminal Is Connected) - Mitsubishi Electric FX3U-232-BD User Manual

Melsec-f fx series programmable controllers data communication edition
Table of Contents

Advertisement

FX Series PLC User's Manual - Data Communication Edition
Inverter Communication
5.8

F800 and A800 Series (when built-in RS-485 terminal is connected)

5.8.1
Contents of parameter setting
1. Contents of communication setting (essential items)
The table below shows parameters which should be set in all cases.
Parameter
Parameter
No.
group
Pr331
N030
Pr332
N031
Pr333
N032
N033
Pr334
N034
Pr337
N037
Pr341
N038
Pr79
D000
Pr340
D001
Pr549
N000
2. Parameters which should be adjusted between test operation and actual operation
Parameter
Parameter
No.
group
Pr335
N035
Pr336
N036
3. Others (which should be set if necessary)
The table below shows parameters to be considered when using various system configuration and inverters.
For the method of use, refer to the respective inverter manual.
Parameter
Parameter
No.
group
Pr342
N001
Pr338
D010
Pr339
D011
Parameter item
RS-485 communication station
RS-485 communication speed
RS-485 communication stop bit length/
data length
RS-485 communication data length
RS-485 communication stop bit length
RS-485 communication parity check
selection
RS-485 communication waiting time
setting
RS-485 communication CR/LF selection
Operation mode selection
Communication startup mode selection
Protocol selection
Parameter item
RS-485 communication number of
retries
RS-485 communication check time
interval
Parameter item
Communication EEPROM write
selection
Communication operation command
source
Communication operation command
source
5 Communication Setting in Inverter
5.8 F800 and A800 Series (when built-in RS-485 terminal is connected)
Set value
Setting contents
00 to 31
Up to eight inverters can be connected.
48
4800 bps
96
9600 bps (standard)
192
19200 bps
384
38400 bps
10
Data length: 7-bit/Stop bit: 1-bit
1
Data length: 7 bits
0
Stop bit: 1 bit
2
2: Even parity
9999
Set in communication data
1
CR: Provided, LF: Not provided
External operation mode is selected
0
when power is turned ON.
1
Computer link
Mitsubishi inverter (computer link)
0
protocol
Set value
Setting contents
Set the value shown on the left during
9999
adjustment, and set a value from 1 to
10 during operation.
Set the value shown on the left during
adjustment, and set a value in
9999
accordance with the system
specification during operation.
Set value
Setting contents
0: Write to EEPROM and RAM.
0 or 1
1: Write to RAM only.
0: PLC
0 or 1
1: Outside
0: PLC
0 or 1
1: Outside
A
B
C
D
E
F
G
H
I
Apx.A
E-67