Inverter Communication
3. IVMC instruction error codes
When errors occur in the send data of the IVMC instruction, the following error codes are stored.
It is recommended to check error codes in hexadecimal.
Refer to the error code list earlier in this section for other errors.
Error code
(HEX)
IVMC
instruction
data2
error
information
information
b15 to b8
b7 to b4
H00
H02
HA to HC
Send
Send
data1
error
error
information
b3 to b0
No error has occurred in both send data 1 and
H0
H0
send data 2.
Normal end
The inverter sent error code HA to send data 1 of
the IVMC instruction.
A parameter was written in a mode other than
HA
computer link mode or while the inverter was
operating. The inverter did not accept the
received data, but was not stopped by alarm.
H0
The inverter sent error code HB to send data 1 of
HB
the IVMC instruction.
Non-existing instruction code was specified.
The inverter sent error code HC to send data 1 of
HC
the IVMC instruction.
Data outside the allowable range was specified.
The inverter sent error code HA to send data 2 of
the IVMC instruction.
A parameter was written in a mode other than
HA
computer link mode or while inverter was
operating. The inverter did not accept the
received data, but was not stopped by alarm.
H0
The inverter sent error code HB to send data 2 of
HB
the IVMC instruction.
Non-existing instruction code was specified.
The inverter sent error code HC to send data 2 of
HC
the IVMC instruction.
Data outside the allowable range was specified.
The inverter sent error codes to both send data 1
and send data 2 of the IVMC instruction.
HA to HC
Refer to the contents of the error of the
corresponding error codes of send data 1 and
send data 2 for details of error codes.
12.4 Details of Related Devices (FX3S, FX3G, FX3GC, FX3U, FX3UC)
Contents of error
12 Related Data
Inverter operation
The
inverter
accepts
data corresponding to
send data 2, and is not
brought to an alarm
stop.
The
inverter
accepts
data corresponding to
send data 1, and is not
brought to an alarm
stop.
The inverter does not
accept data
corresponding to send
data 1 and 2, but is not
brought to an alarm
stop.