When Combined With Programming Communication - Mitsubishi Electric FX3U-232-BD User Manual

Melsec-f fx series programmable controllers data communication edition
Table of Contents

Advertisement

FX Series PLC User's Manual - Data Communication Edition
Non-Protocol Communication (RS/RS2 Instruction)
10.4

When Combined with Programming Communication

In FX
, FX
3S
3G
changed over to communication with a programming tool (programming communication) by the following
methods.
If the external equipment executes another type of communication while the programming communication is
selected, the PLC sends back "NAK".
In FX
, FX
, FX
3S
3G
can be checked in the operation mode display devices (D8389, D8419 and D8439).
1. When changing over using RUN mode and STOP mode
Set the communication format as shown below to use non-protocol communication (in accordance with RS-
232C) using the RS2 instruction while in RUN mode and then use the programming communication while in
STOP mode.
Make sure to set the communication format used in the RS2 instruction to D8370, D8400 or D8420, and write
it before executing the RS2 instruction.
X0
Command
RS2 D1
2. When changing over using the RS2 instruction while in RUN mode
When changing over non-protocol communication using the RS2 instruction to the programming
communication while in RUN mode, set the RS2 instruction to OFF, and then overwrite the communication
format (D8370, D8400 or D8420) to "H0000".
Before starting up the RS2 instruction again, make sure to properly overwrite the communication format
(D8370, D8400 or D8420) used in the RS2 instruction.
X0
RS2 D1
X0
3. Caution on using the RS2 instruction and programming communication together
Do not use the communication setting by parameters. Use the communication format device (D8370, D8400
or D8420).
F-82
, FX
, FX
and FX
3GC
3U
3UC
, FX
and FX
3GC
3U
3UC
MOV
H0086 D8400
P
K1
D2
K1
K1
MOV
H0086 D8400
P
K1
D2
K1
K1
MOV
H0000 D8400
P
10 When Combined with Another Communication
PLCs, non-protocol communication using RS2 instruction can be
PLCs, the communication type operating in the communication port
10.4 When Combined with Programming Communication

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents