FX Series PLC User's Manual - Data Communication Edition
Inverter Communication
5.

Communication Setting in Inverter

Before connecting an inverter to a PLC, set parameters related to communication in the inverter parameter
unit (PU) in advance using the procedure described in this chapter.
If these parameters are overwritten from the PLC after the inverter is connected, communication will be
disabled.
If these parameters are changed by mistake, they should be set again.
5.1
Communication Port and Applicable Parameters
When connecting an inverter to a PLC, it is necessary to set parameters corresponding to the communication
port in advance.
S500 Series
Remove the surface cover.
RS-485 port
(PU connector)
F700 and A700 Series
Remove the surface cover.
RS-485 terminal
D700 Series
Remove the surface cover.
PU connector
E-48
E500 Series
Remove the operation panel.
PU
connector
E700 Series
Open the PU connector cover.
PU connector
F800, A800 Series
Remove the surface cover.
RS-485
terminal
5 Communication Setting in Inverter
5.1 Communication Port and Applicable Parameters
A500, F500 and V500 Series
Remove the operation panel.
PU
connector
FR-A5NR
Remove the
surface cover
Remove the surface cover.
FR-E7TR