FX Series PLC User's Manual - Data Communication Edition
Inverter Communication
*Inverter B
(station number 1)
M510
Driving of
write
instruction
(station
number 1)
M8029
Instruction execute
complete
*1.
When using an E500 Series inverter, use "H2" to specify computer link operation.
*2.
The FX
, FX
3S
instead.
FNC271
K1
H0FD
IVDR
FNC271
K1
H0FB
IVDR
FNC 12
MOV
FNC 12
MOV
FNC 12
MOV
FNC 12
MOV
FNC 12
MOV
FNC 12
MOV
FNC 12
MOV
FNC 12
MOV
FNC274
K1
K4
*2
IVBWR
and FX
PLC does not support the IVBWR instruction. Use the IVWR instruction
3G
3GC
10 Practical Program Examples (FX3S, FX3G, FX3GC, FX3U, FX3UC)
H9696
K1
The inverter is reset
(station number 1)
Computer link operation
H0
*1
K1
is specified
(station number 1)
The maximum
K1
D700
frequency (Pr. 1) is
P
specified
(station number 1)
The maximum
K12000
D701
frequency (Pr. 1) is
P
set to "120 Hz"
(station number 1)
The minimum
K2
D702
frequency (Pr. 2) is
P
specified
(station number 1)
The minimum
K500
D703
frequency (Pr. 2) is
P
set to "5 Hz"
(station number 1)
The acceleration time
K7
D704
(Pr. 7) is specified
P
(station number 1)
The acceleration time
K10
D705
(Pr. 7) is set to "1 sec"
P
(station number 1)
The deceleration time
K8
D706
(Pr. 8) is specified
P
(station number 1)
The deceleration time
K10
D707
(Pr. 8) is set to "1 sec"
P
(station number 1)
The parameters are written
D700
K1
all at once
D700 to D707
(Pr. 1, Pr. 2, Pr. 7 and Pr. 8)
(station number 1)
RST
M510
Driving of
write
instruction
(station
number 1)
10.2 Practical Example 2
A
B
C
D
E
F
G
H
I
Apx.A
E-127