FX Series PLC User's Manual - Data Communication Edition
Inverter Communication
5.7.2

Parameter setting method (reference)

This subsection explains the parameter setting method using the operation panel.
For details on the operation panel, refer to the respective inverter manual.
Monitor (4-digit LED)
shows the frequency,
parameter number, etc.
Setting dial
Used to change the
frequency setting and
parameter values.
The operating procedure example below shows a case in which the baud rate is set to 19200 bps.
1
Confirming the RUN indicator and the operation mode indicator
Confirm that the operation is stopped (that the RUN indicator is off).
2
Selecting the parameter setting mode
Press the MODE key, and select the parameter setting mode.
Monitor/frequency
setting mode
3
Setting the parameter Pr. 160 to "0"
(This step is not required if Pr. 160 is already set to "0".)
1. Turn the setting dial until "Pr. 160" is displayed.
2. Press the SET key to read the current set value.
3. Turn the setting dial, and change the set value to "0".
Parameter setting mode
The previously read parameter
is displayed.
5 Communication Setting in Inverter
5.7 F700 and A700 Series (when built-in RS-485 terminal is connected)
Operation mode indicator
NET: Lit to indicate network
operation mode
Rotation direction indicator
FWD: Lit during forward rotation
REV: Lit during reverse rotation
MODE key
Changes over the mode.
SET key
Sets each setting.