Data Transfer Error Code [D8211 To D8218] [D211 To D218] - Mitsubishi Electric FX3U-232-BD User Manual

Melsec-f fx series programmable controllers data communication edition
Table of Contents

Advertisement

FX Series PLC User's Manual - Data Communication Edition
N:N Network

10.2.18 Data transfer error code [D8211 to D8218] [D211 to D218]

These devices store the error code in the master station and slave stations.
1. Stations requiring program setting
The master station requires program setting.
However, this setting for the station itself is not required.
2. Detailed contents
1) The device used varies depending on the FX Series.
FX Series
FX
, FX
, FX
1N
1NC
FX
, FX
, FX
3S
3G
FX
, FX
0N
1S
2) Error code list
Error
Error name
code
01H
Monitoring timeout
Station number
02H
error
03H
Counter error
Message format
04H
error
11H
Monitoring timeout
Message format
14H
error
Slave station no
21H
response error
Station number
22H
error
23H
Counter error
Parameter not
31H
received
M: Master station, L: Slave station
*1.
Any slave station other than the slave station in which error occurred
*2.
Station in which error occurred
3. Cautions on use
Data transfer sequence errors that occurred within the station itself cannot be detected.
Do not change the preset numeric value using a program or programming tool.
B-66
Master
station
, FX
,
2N
2NC
D8211
, FX
, FX
3GC
3U
3UC
D211
Station
in which
error
occurred
L
L
L
L
M
M
L
L
L
L
Slave
Slave
Slave
station
station
station
No. 1
No. 2
No. 3
D8212
D8213
D8214
D212
D213
D214
Station
which
Contents of error
detected
error
Slave station did not respond to the
M
sending request from the master station
within the monitoring time.
An unexpected slave station responded
M
to the sending request by the master
station.
The counter value included in the
M
parameter data is different from the
counter value given by a slave station.
The message given by the slave station
M, L
is incorrect.
The master station did not give a sending
L
request to the next slave station within
the monitoring timer.
The message from the master station is
L
incorrect.
*1
The specified slave station does not exist.
L
An unexpected slave station responded
*1
to the sending request by the master
L
station.
The counter value included in the
*1
parameter data is different from the
L
counter value given by a slave station.
Before parameters had been received,
*2
sending request was received from the
L
master station.
10.2 Details of Related Devices
Slave
Slave
Slave
station
station
station
No. 4
No. 5
No. 6
D8215
D8216
D8217
D215
D216
D217
Check point
Wiring and power
supply
Station number
settings
Wiring
Wiring, power
supply and station
number settings
Wiring and power
supply
Wiring, power
supply and station
number settings
Wiring, power
supply and station
number settings
Station number
settings
Wiring
Wiring and power
supply
10 Related Data
Slave
station
No. 7
D8218
D218

Hide quick links: