Installation
Switchgear storage in
closed rooms
Outdoor storage of
switchgear packed in
seaworthy crates
60/172
As a rule, the switchgear should be stored in a closed room. The storage room must have the
following characteristics:
• Floor with adequate load-bearing capacity (weights as per delivery note)
• Even floor to enable stable storage
• Well-ventilated and free of dust as far as possible
• Dry and protected against humidity and vermin (e.g. insects, mice, rats)
• Heatable to at least 2 °C above the outside temperature in order to prevent condensation.
• Check humidity in the packings every 4 weeks (condensation)
• Do not unpack small parts to avoid corrosion and loss.
If the switchgear or parts thereof are delivered in seaworthy crates, these can be stored up to 6
months in other rooms or outdoors. The storage place must have the following characteristics:
• Floor with adequate load-bearing capacity (weights as per delivery note)
• Protected against humidity (rain water, flooding, melting water from snow and ice),
pollution, vermin (rats, mice, termites, etc.) and unauthorized access
• Place all crates on planks and square timber for protection against floor humidity.
• After 6 months of storage, have the desiccant agent regenerated professionally. To do this,
ask for expert personnel via your regional Siemens representative.
12.3

Tools/auxiliary means

Before starting to work on the switchgear, provide for the tools/auxiliary means required:
• Hexagonal screwdriver insert (min. length 140 mm) for hexagon socket-head bolt 10 mm
DIN 7422
• Torx screwdriver T25
• Torque wrench 20 - 50 Nm
• Ratchet, reconnectable DIN 3122
• Extension DIN 3123 40 - 125
• Socket spanner inserts DIN 3124, socket spanner inserts size 17 and 18, min. length 80 mm
• Water level
• Lifting truck
• Reinforcing bars, roller crowbars
• Transport rollers, tubes
• Lifting rods, length 753 mm, Ø 20 mm, e.g. certified lifting rods (order number 802-9047.3,
to be procured from the regional Siemens representative)
• Lifting rods, length 1900 mm, Ø 20 mm for panel groups of up to 3 panels, e.g. certified
lifting rods (order number 036-1161.3, to be procured from the regional Siemens
representative)
• Additionally, solutions for special transport rods are available on request if there is not
enough space at the place of installation to remove the transport rods after transport.
12.4

Installation and fixing material

Before starting to install the individual components, provide for the required installation and
fixing material.
Revision 05 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C Wind • 802-9074.9