Siemens NXPLUS C Installation And Operating Instructions Manual page 83

Medium-voltage switchgear/wind fixed mounted circuit-breaker switchgear up to 36 kv, extendable
Table of Contents

Advertisement

Fig. 68:
Mounted voltage transformers (overview)
Fig. 69:
Voltage transformer mounted on the busbar (sectional view from the front)
802-9074.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C Wind • Revision 05
Installation of the voltage transformers
ATTENTION!
The voltage transformer bushings may be damaged during installation.
During installation, protect the voltage transformer bushings from damage (lifting, setting
down). Do not remove the protective caps of the voltage transformers until right before
installation.
Voltage transformer (3x)
Storage box
Voltage transformer frame
Nut-and-washer assembly M8 (12x)
3D washer (12x)
Bolt-and-washer assembly M8x20 (12x)
Cast-resin cone of voltage transformer
Centering nut (tightening torque: 10 Nm)
Hexagonal nut M12 * (tightening torque: 50 Nm)
Strain washer *
Contact half-shell *
Threaded bolt M12 / M16, tightening torque: 10 Nm *
* These components are already pre-assembled on the adapter
Installation
83/172

Advertisement

Table of Contents
loading

Table of Contents