Siemens NXPLUS C Installation And Operating Instructions Manual page 45

Medium-voltage switchgear/wind fixed mounted circuit-breaker switchgear up to 36 kv, extendable
Table of Contents

Advertisement

Three-position
disconnector
Three-position switch-
disconnector
802-9074.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C Wind • Revision 05
Function
Class
DISCONNECTING
M0
READY-TO-EARTH
M0, E0
EARTHING
E2
1)
By closing the circuit-breaker
Application in the ring-main panel
Function
Class
DISCONNECTING
M0
LOAD BREAKING
M1
E3
EARTHING
M0
E2
2)
Additionally to I
, the class also covers the test currents I
load2
Standard
Property
IEC 62 271-102 1000 times mechanically without maintenance
IEC 62 271-102 1000 times mechanically without maintenance
IEC 62 271-200 5 times rated short-circuit making current I
1)
IEC 62 271-102
maintenance
Standard
Property
IEC 62 271-102 1000 times mechanically without maintenance
IEC 62 271-103 1000 times mechanically without maintenance
IEC 62 271-103 100 times rated mainly active load-breaking current
I
load2
circuit making current I
IEC 62 271-102 1000 times mechanically without maintenance
IEC 62 271-102 5 times rated short-circuit making current I
maintenance
load1
2)
without maintenance, 5 times rated short-
without maintenance
ma
, I
, I
, I
and I
, I
and I
loop
cc2
cc2
Ic
ef1
Description
without
ma
without
ma
ef2