Indications
WEGA 1.2, WEGA 2.2
802-9074.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C Wind • Revision 05
24.3

Indications WEGA 1.2, WEGA 2.2

DANGER!
High voltage! Danger! Verify safe isolation from supply without any doubt!
Possible sources of failure:
- Defective voltage indicator (or device for function testing of the coupling section)
- Maloperation of the voltage indicator (or device for function testing of the coupling
section)
Use only voltage indicators or devices according to EN 61 243-5 / IEC 61 243-5 /
VDE 0682-415 to test the function of the coupling section. (The interface conditions have
not changed as against the old standard VDE 0681 Part 7; the corresponding indicators can
still be used.)
Fig. 142: Operating elements
WEGA 1.2/2.2
Indication
WEGA 1.2
L1
L2
L3
A0
A1
A2
A3
A4
A5
A6
LC display (illuminated for WEGA 2.2)
"Display Test" button
Test socket L1
Test socket L2
Earth socket
Test socket L3
WEGA 2.2
L1
L2
L3
For WEGA 2.2: Operating voltage not present, auxiliary power
present, LCD illuminated
• Operating voltage present
• For WEGA 2.2: Auxiliary power present, LCD illuminated
• Operating voltage not present
• For WEGA 2.2: Auxiliary power not present, LCD not
illuminated
• Failure in phase L1, operating voltage at L2 and L3
• For WEGA 2.2: Auxiliary power present, LCD illuminated
• Voltage present, current monitoring of coupling section
below limit value
• For WEGA 2.2: Auxiliary power present, LCD illuminated
• Indication: "Display Test" passed
• For WEGA 2.2: Auxiliary power present, LCD illuminated
For WEGA 2.2: LCD for missing auxiliary voltage is not
illuminated