Siemens NXPLUS C Installation And Operating Instructions Manual page 107

Medium-voltage switchgear/wind fixed mounted circuit-breaker switchgear up to 36 kv, extendable
Table of Contents

Advertisement

Installation position
Principle of installation
Installation of cable-type
current transformers
802-9074.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C Wind • Revision 05
Cable-type current transformers in the circuit-breaker panel
The transformer mounting plate is pre-assembled on the cable bracket at the factory. The
cable-type current transformers are supplied in the cable compartment and must be mounted
on the high-voltage cables on site.
Fig. 97:
Installation position of cable-type current
transformers in the circuit-breaker panel
Fig. 98:
Cable connection with cable-type current transformers type WIC1-WE2AS1
Cable plug
High-voltage cable
Transformer mounting plate
Cable-type current transformer
Earthing point
Undo the cable compartment cover.
Take the supplied cable-type current transformers
Push the cable-type current transformers
Mount the cable plugs
Position the pre-assembled transformer mounting plate
way that all 3 cable-type current transformers can be mounted.
Cable shield
Cable clamp
Plain washer A6.4 (4x)
Hexagonal nut M6 (4x)
Saucer-head bolt M6x20 (4x)
on the high-voltage cables.
according to the manufacturer's instructions.
Cable plug
Cable shield
Transformer mounting plate
Cable-type current
transformer
Cable clamp
out of the cable compartment.
at the cable bracket in such a
Installation
107/172