Installation
Mounting the sealing
strip in case of free-
standing arrangement
Joining panels
70/172
To mount the sealing strip, use the Torx screws from the pressure relief duct. Take the other
screws from the supplementary equipment.
Fig. 57:
Mounting sealing strips on rear wall of switchgear
ATTENTION!
If the bolts are tightened too much, the frame may be distorted and the felt strip may become
stiff.
Tighten the bolts M5x16 only until the felt is pressed slightly together.
Bolt two adjacent panels together at the fixing straps
M8x20 and a nut-and-washer assembly.
Bolt the two panels together at the 4 positions
(TORX).
Check whether the bolted panels are in vertical position.
Revision 05 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C Wind • 802-9074.9
with a panel connecting bolt
with thread-ridging screws M5x16
Sealing strip
Sealing strips,
mounted