802-9074.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C Wind • Revision 05
If the high low-voltage compartments are already pre-assembled, the operations to be
performed are the same as those for installation of the protection against vertically falling
water drops on small low-voltage compartments.
Fig. 111: Protection against vertically falling water drops on the left-end panel
(example with high low-voltage compartment) - view from the rear
Connecting plate
Sealing strap for connecting plate
Left end plate
If the low-voltage compartments are not pre-assembled, provide sealing straps at the
following positions:
- Between the individual panels.
- On the rear wall of the low-voltage compartment, in line with the busbar cover.
Fig. 112: Sticking sealing straps on high low-voltage compartments
(example with high low-voltage compartment) - view from
the rear
Sealing strap for left end plate
Top plate
Angle plate
Sealing straps
between the panels
Sealing straps on
the rear wall of the
low-voltage
compartment
Installation
117/172