Siemens NXPLUS C Installation And Operating Instructions Manual page 51

Medium-voltage switchgear/wind fixed mounted circuit-breaker switchgear up to 36 kv, extendable
Table of Contents

Advertisement

Core drillings
(incl. new plug systems)
802-9074.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C Wind • Revision 05
ATTENTION!
For perfect installation of the cable plugs, the following must be observed:
Observe the specifications of the cable manufacturers.
Drilling diameters depend on the cable cross-section!
Fig. 34:
Core drillings - circuit-breaker panel 630 A
1st cable
2nd cable
Conductor distances for circuit-breaker panel
Make
1st cable
Plug type
Nexans
M400TB/G
Euromold
M430TB/G
M440TB/G
Südkabel
SEHDT33
nkt cables
CB36-630
CB36-630
CB36-630 (1250)
CB36-630 (1250)
Tyco Electronics
RSTI-66xx
Raychem
RSTI-66Lxx
RSTI-68xx
RSTI-69xx
* Distance from center of cable to front edge of base frame support
Width of base frame support max. 80 mm
2nd cable
Distance*
Plug type
Distance*
[mm]
[mm]
408
M400TB/G
163
408
M300PBM-630
303
408
M440TB/G
163
408
SEHDT33
143
408
CC36-630
298
408
CB36-630
228
408
CC36-630
298
(1250)
408
CB36-630 (1250) 228
408
RSTI-CC-66xx
293
408
RSTI-66CP-M16
233
408
RSTI-CC-68xx
308
408
RSTI-CC-69xx
308
Installation
51/172