Siemens NXPLUS C Installation And Operating Instructions Manual page 116

Medium-voltage switchgear/wind fixed mounted circuit-breaker switchgear up to 36 kv, extendable
Table of Contents

Advertisement

Installation
Fig. 110: Protection against vertically falling water drops on the left-end panel
(example with small low-voltage compartment) - view from the front
116/172
Fig. 109: Completed protection against vertically falling water drops
(example with small low-voltage compartment) - view from the front
Mounting the protection against vertically falling water drops on the end panel
Mounting the protection against vertically falling water drops on a high low-voltage
compartment
ATTENTION!
Please observe the following instructions to mount the protection against vertically falling
water drops on a high low-voltage compartment if the low-voltage compartments are not pre-
assembled:
Stick a sealing strap in line with the upper edge of the busbar cover and on the rear wall of
the low-voltage compartment.
Stick a sealing strap between the panels on the rear wall of the low-voltage compartment,
in line with the partition plate.
Revision 05 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C Wind • 802-9074.9
Connecting plate
Sealing strap for connecting plate
Angle plate
Mounted roof plate
Low-voltage compartment
Busbar cover
Roof plate
Sealing strap for left end plate
Left end plate