Siemens NXPLUS C Installation And Operating Instructions Manual page 104

Medium-voltage switchgear/wind fixed mounted circuit-breaker switchgear up to 36 kv, extendable
Table of Contents

Advertisement

Installation
Connecting two or three
cables per phase
104/172
Up to 2 cables (plugs) can be connected per phase for 600-mm-wide panels and up to 3 cables
(plugs) per phase for 450-mm-wide panels.
After cable installation on the three phases, one arcing plate each must be mounted in the
cable compartment. In like manner, the associated floor plate of the pressure-resistant floor
cover must be mounted after each installed row of cable T-plugs (see page 97, "Mounting the
pressure-resistant floor cover").
NOTE!
The arcing plates in the cable compartment have been pre-assembled at the factory. For cable
installation, the arcing plates must be removed.
After cable installation, position the arcing plates as close as possible to the front in
accordance with the cable T-plugs used.
Do not exceed the distance of 10 mm to the cable T-plugs.
After installation, the arcing plates must not touch the cable T-plugs.
While installing the arcing plates, take care not to damage the cable T-plugs.
Fig. 93:
Circuit-breaker panel, 600 mm: Arcing plates at the
cable connection, two cables per phase
Fig. 94:
Disconnector panel and ring-main panel, 450 mm:
Arcing plates at the cable connection, three cables per
phase
Push rubber sleeves onto cable T-plugs.
Mount first set of cable T-plugs on phases L1 to L3.
Mount the floor plate of the pressure-resistant floor cover (see page 97, "Mounting the
pressure-resistant floor cover").
Revision 05 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C Wind • 802-9074.9
Fastening at the partition to
the operating mechanism
compartment
Cable T-plug
Arcing plate