Siemens NXPLUS C Installation And Operating Instructions Manual page 64

Medium-voltage switchgear/wind fixed mounted circuit-breaker switchgear up to 36 kv, extendable
Table of Contents

Advertisement

Installation
Removing from the
wooden pallets
64/172
If the panels are equipped with an interlock for the cable compartment cover, the panels must
be earthed to remove the cable compartment cover.
Remove PE foil.
Undo the bolted joint of the cable compartment cover at the front. Depending on the panel
width, there are two or four self-tapping screws.
Fig. 46:
Bolted joints of cable compartment cover
If cable compartment cover is interlocked: Push the locking device lever
keep it in this position.
Fig. 47:
Front plate with mimic diagram on the circuit-
breaker panel
Revision 05 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C Wind • 802-9074.9
450 mm: Disconnector panel and ring-
main panel
600 mm: Circuit-breaker panel
upwards and
"Feeder earthed" locking device