To push the control gate from the right or left position to the center position again:
Remove the stopper (according to the position of the control gate), and push the solenoid
back with the screwdriver. Push the control gate to the center position. The solenoid is
released again, blocking further movements.
After work completion, pull the screwdriver out and refit the dummy plug.
Tripping the emergency release in the ring-main panel:
ATTENTION!
The solenoid openings in the ring-main panel are covered with the front plate.
Remove the front plate in the ring-main panel.
Fig. 115: Solenoid openings in the ring-main panel
To push the control gate from center position to upper position: Insert the screwdriver
through the upper opening
The upper solenoid is released again, blocking further movements.
To push the control gate from center position to lower position: Insert the screwdriver
through the lower opening
downwards. The lower solenoid is released again, blocking further movements.
To push the control gate from the upper or lower position to the center position again:
Insert the screwdriver (according to the position of the control gate), and push the solenoid
back. Push the control gate to the center position. The solenoid is released again, blocking
further movements.
After work completion, pull the screwdriver out and refit the front plate.
Revision 05 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C Wind • 802-9074.9
and push the solenoid back. Push the control gate upwards.
and push the solenoid back. Push the control gate