Connecting Surge Arresters - Siemens NXPLUS C Installation And Operating Instructions Manual

Medium-voltage switchgear/wind fixed mounted circuit-breaker switchgear up to 36 kv, extendable
Table of Contents

Advertisement

Installation
108/172
Bolt the cable-type current transformers
4 saucer-head bolts
Lead the cable shield
at the earthing point
Swing the high-voltage cables
and connect the cable plugs
plugs").
Mount the cable compartment cover.
15.4

Connecting surge arresters

Suitable surge arresters are listed in the operating instructions (see page 22, "Possible
combinations of cable connection types (T-plugs, coupling inserts) and surge arresters in
NXPLUS C Wind up to 36 kV").
NOTE!
For certain surge arrester types in the circuit-breaker panel, the surge arresters protrude
through the floor cover into the cable basement (see page 22, "Cable connection").
Provide additional core drillings for the surge arresters.
The surge arresters are supplied with the supplementary equipment. Depending on their
version, they are pre-assembled with a support.
If a power-frequency voltage test is planned at site after installation (see page 126,
"Performing the power- frequency voltage test"), do not fit the surge arresters and cables yet.
Mount the surge arresters according to the manufacturer's assembly instructions.
Ensure earth connection of the surge arrester according to the manufacturer's assembly
instructions.
Fig. 99:
Mounted surge arrester (example)
Revision 05 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C Wind • 802-9074.9
onto the transformer mounting plate
, washers
and hexagonal nuts
back through the cable-type current transformer
.
in together with the cable-type current transformers
to the cable feeder (see page 99, "Connecting cable T-
using
each.
, and bolt tight
,