Table 4-24 Program Contents - Honeywell UDC3200 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3200:
Table of Contents

Advertisement

Monitoring and Operating the Controller
Associated
Prompts
STRT SEG
Start segment
number
END SEG
End segment
number
RECYCLES
Recycle number
STATE
Program state
PROG END
Program
termination state
KEYRESET
Reset Program
(ToBEGIN)
to Beginning
KEYRESET
Rerun current
(RERUN)
segment
HOTSTART
Hot Start
126

Table 4-24 Program Contents

Contents
The start segment number designates the number of the first
segment.
Range = 1 to 11
The end segment number designates the number of the last
segment, it must be a soak segment (even number). Range =
2 to 12
The recycle number allows the program to recycle a specified
number of times from beginning to end. Range = 0 to 99
The program state selection determines the program state
after completion.
The selections are:
• DISABLE = program is disabled (so program value
changed to DISABLE)
• HOLD = program on hold
The program termination state function determines the status
of the controller upon completion of the program.
The selections are:
• LAST = controls to last setpoint
• FAILSAFE = manual mode and failsafe output.
When enabled, this selection allows you to reset the program
via the keyboard to the beginning of the program.
When enabled, this selection allows you to reset the program
via the keyboard to the beginning of the current segment.
This function determines whether LSP1 or PV is used as the
setpoint when the program is initially changed from HOLD to
RUN.
The selections are:
DISABLE = When the program is initially changed from HOLD
ENABLE = When the program is initially changed from HOLD
UDC3200 Universal Digital Controller Product Manual
Definition
to RUN the present LSP1 value is captured as
the default setpoint. If the program is terminated
or the power cycled before the program has
completed, the LSP1 is used as the control
setpoint. The beginning segment uses this value
as the initial ramp setpoint.
to RUN the present PV value is captured and
used as the beginning setpoint value for the ramp
segment. If the program is terminated before
completion, the setpoint value will revert back to
the PV value captured at the initial HOLD to RUN
transition. If the power is cycled before program
completion, upon power-up the setpoint is set to
12/04