Device functions Proline Prosonic Flow 93
Endress+Hauser
9.3
Group SYSTEM PARAMETER (CH1...CH2)
9.3.1

Function group CONFIGURATION

BASIC FUNCTION
G
BASIC FUNCTION
INSTALLATION
Use this function to reverse the sign of the flow quantity, if necessary.
DIRECTION SENSOR
(6600)
Options:
NORMAL
INVERSE
Factory setting:
NORMAL
FLOW DAMPING
!
(6603)
The system damping acts on all functions and outputs of the measuring device.
Use this function to set the filter depth of the digital filter. This reduces the sensitivity of
the measuring signal to interference peaks (e.g. high solids content, gas bubbles in the
fluid, etc.). The system reaction time increases with the filter setting.
User input:
0...100 s
Factory setting:
0
POSITIVE
Use this function to interrupt evaluation of measured variables. This is necessary when a
ZERO RETURN
piping system is being cleaned, for example. This setting acts on all function and outputs
(6605)
of the measuring device.
Options:
OFF
ON
Factory setting:
OFF
HART
GAA
PROCESS PARAM. CH1
GIA
PROCESS PARAM. CH2
GIB
SYSTEM PARAM. CH1
GLA
SYSTEM PARAM. CH2
GLB
Functional description
SYSTEM PARAMETER CH1
Note!
Signal output is set to the "ZERO FLOW" value.
9 Block BASIC FUNCTION
CONFIGURATION
CONFIGURATION
CONFIGURATION