5.10 Changing operation panel display

5.10.1 Changing the unit (A/V) from a percentage of current
f701 :Current/voltage unit selection
 Function
Current 100% = Rated current of inverter
Voltage 100% = 200Vac (200V class), 400Vac (400V class)
 Example of setting
During the operation of the VFS15-2015PM (rated current: 8.0A) at the rated load (100% load), units are
5
displayed as follows:
1) Display in percentage terms
[Parameter setting]
Title
f701
*
and voltage
These parameters are used to change the unit of monitor display.
%  A (ampere)/V (volt)
%
Output current:
 
100%
%
Input voltage:
 
100%
Function
Current/voltage unit
selection
The f701 converts the following parameter settings:
 A display : Current monitor display: Load current, torque current
Motor electronic-thermal protection level 1 & 2
DC braking current
Stall prevention level 1 & 2
Small current detection current
Brake releasing small current detection level
 V display : Voltage monitor display: Input voltage, output voltage
V/f 5-point setting VF1-5 voltage
Note) Base frequency voltage 1 & 2(, ) always displayed in the unit of V.
2) Display in amperes/volts
Output current:

8.0A
Input voltage:

200V
Adjustment range
0: %
1: A (ampere) / V (volt)
, f173
f251
f601, f185
f611
f326
f191, f193, f195, f197, f199
E-22
E6581926
Default setting
0