Toshiba Tosvert VF-S15 Instruction Manual page 189

Industrial inverter (for 3-phase induction motors)
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

 Function
 Refer to "PID control instruction manual: E6581879" for details.
[Parameter setting]
Title
fpid Process input value of PID control
f359
f360
f361 Delay filter
f362
f363
f366
f367 Process upper limit
6
f368 Process lower limit
f369 PID control feedback signal selection
f372
f373
f380
f389
*1: These are parameters set by setup menu. Default setting value is "jp". Refer to section 11.5.
Process control including keeping airflow, pressure, and the amount of flow constant, can be
exercised using feedback signals (4 to 20mA, 0 to 10V) from a detector.
Or, it is also possible to always set 0 for integral and differential at terminal input.
Function
PID control waiting time
PID control
Proportional gain
Integral gain
Differential gain
Process increasing rate (speed type
PID control)
Process decreasing rate (speed type
PID control)
PID forward/reverse characteristics
selection
PID control reference signal selection
Adjustment range
f368 -  (Hz)
0-2400 (s)
0: Disabled
1: Process type PID control
2: Speed type PID control
0.0-25.0 (s)
0.01-100.0
0.01-100.0
0.00-2.55
0.0-fh (Hz)
0.0- (Hz)
0: Disabled
1: Terminal VIA
2: Terminal VIB
3: Terminal VIC
4 to 6: -
0.1-600.0 (s)
0.1-600.0 (s)
0: Forward
1: Reverse
0: fmod/f207 selected
1: Terminal VIA
2: Terminal VIB
3: fpid
4: RS485 communication
5: UP/DOWN from external logic
input
6: CANopen communication
7: Communication option
8: Terminal VIC
9, 10: -
11: Pulse train input
F-78
E6581926
Default setting
0.0
0
0
0.1
0.30
0.20
0.00
60.0 *1
0.0
0
10.0
10.0
0
0