Toshiba Tosvert VF-S15 Instruction Manual page 208

Industrial inverter (for 3-phase induction motors)
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

Title
f500
f501
f504
f510 Acceleration time 3
f511 Deceleration time 3
f519
 Default setting is 0.1s unit. Acceleration/deceleration time unit can be changed to 0.01s unit by f519=1
setting. (The value of f519 return to 0 after setting.)
1)
Output frequency [Hz]
6
=
=
=
2)
Title
f505
f513
Note: Acceleration/deceleration patterns are changed from pattern 1 to pattern 2 and from pattern 2 to pattern 3
in increasing order of frequency, regardless of the order in which frequencies are changed. (For example,
if f505 is larger than f513, f513 pattern 1 is selected in the frequency range below the frequency
set with f505.)
Function
Acceleration time 2
Deceleration time 2
Acceleration/deceleration selection
(1, 2, 3) (Panel keypad)
Setting of acceleration/deceleration
time unit
Selection using parameters

0



Acceleration/deceleration time 1 is initially set as the default. Acceleration/deceleration time 2 and 3 can
be selected by changing the setting of the f504.
Enabled if cmod= (panel input enabled)
Switching by frequencies (Switching the acceleration/deceleration time automatically at the setting
frequency)
Function
Acceleration/deceleration 1 and 2
switching frequency
Acceleration/deceleration 2 and 3
switching frequency
Adjustment range
0.0-3600 (0.00-360.0) [sec]
0.0-3600 (0.00-360.0) [sec]
1: Acceleration/deceleration 1
2: Acceleration/deceleration 2
3: Acceleration/deceleration 3
0.0-3600 (0.00-360.0) [sec]
0.0-3600 (0.00-360.0) [sec]
0: -
1: 0.01s unit (after execution: 0)
2: 0.1s unit (after execution: 0)


Adjustment range
0.0 (disabled)
0.1-(Hz)
0.0 (disabled)
0.1-(Hz)
F-96
E6581926
Default setting
10.0
10.0
1
10.0
10.0
0
Time [s]

Default setting
0.0
0.0