Toshiba Tosvert VF-S15 Instruction Manual page 305

Industrial inverter (for 3-phase induction motors)
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

Communication
Title
Function
No.
0316
PWM carrier

frequency control
mode selection
0317
Synchronized

deceleration time
(time elapsed
between start of
deceleration to stop)
0318
Synchronized

acceleration time
(time elapsed
between start of
acceleration to
achievement of
specified speed)
0319
Regenerative

over-excitation
upper limit
0320
Droop gain

0323
Droop insensitive

torque band
0324
Droop output filter

0325
Brake releasing

waiting time
0326
Brake releasing

small current
detection level
0327
Factory specific

coefficient 3C
0328
Light-load high-

speed operation
selection
0329
Light-load high-

speed learning
function
0330
Automatic light-load

high-speed
operation frequency
0331
Light-load high-

speed operation
switching lower
limit frequency
*1: These are parameters set by setup menu. Default setting value is "jp". Refer to section 11.5.
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.
*12: When f701=1, adjustment range is 100%=rated current, or 100%=200V(200V class)/ 400V(400V class).
Minimum
setting unit
Unit
Adjustment range
Panel/Commun
ication
-
-
0: Carrier frequency without reduction
1: Carrier frequency with automatic
reduction
2: Carrier frequency without reduction
Support for 400V models
3: Carrier frequency with automatic
reduction
Support for 400V models
s
0.1/0.1
0.0-3600 (360.0)
s
0.1/0.1
0.0-3600 (360.0)
%
1/1
100-160
%
0.1/0.1
0.0-100.0
%
1/1
0-100
-
0.1/0.1
0.1-200.0
s
0.01/0.01
0.00-2.50
%
1/1
0-100 *12
(A)
-
-
-
-
-
0:Disabled
1:High-speed operation speed set
automatically (Power running at F
command: Increase)
2:High-speed operation speed set
automatically (Power running at R
command: Increase)
3:High-speed operation speed set
with f330 (Power running at F
command: Increase)
4:High-speed operation speed set
with f330 (Power running at R
command: Increase)
-
-
0:No learning
1:Forward run learning
2:Reverse run learning
Hz
0.1/0.01
30.0-ul
Hz
0.1/0.01
5.0-ul
K-11
E6581926
Default
User
Reference
setting
setting
1
6.18
2.0
6.19.2
2.0
140 *1
6.19.5
0.0
6.20
10
100.0
0.00
6.22.1
0
-
* 3
0
6.21
0
60 *1
40.0
11