Voltage
class
3 phase
200V
class
1 phase
200V
class
3 phase
400V
Class
*1: For Japan: JEAC8001-2005 compliant
Note 1: Sizes of the wires connected to the input terminals R/L1, S/L2 and T/L3 (Single-phase models are R/L1
10
Note 2: For the control circuit, use shielded wires 0.75 mm
Note 3: For grounding, use wires with a size equal to or larger than the above.
Note 4: The wire sizes specified in the above table apply to HIV wires (copper wires shielded with an insulator
Wire size (mm
Applicable
Braking resistor
motor
(optional)
(kW)
IEC
For Japan
Compliant
*1
0.2
1.5
2.0
0.4
1.5
2.0
0.75
1.5
2.0
1.5
1.5
2.0
2.2
1.5
2.0
3.7
2.5
2.0
5.5
4.0
2.0
7.5
6.0
3.5
11
16
5.5
15
25
14
0.2
1.5
2.0
0.4
1.5
2.0
0.75
1.5
2.0
1.5
1.5
2.0
2.2
1.5
2.0
0.4
1.5
2.0
0.75
1.5
2.0
1.5
1.5
2.0
2.2
1.5
2.0
3.7
1.5
2.0
5.5
1.5
2.0
7.5
2.5
2.0
11
4.0
2.0
15
6.0
3.5
and S/L2/N) and the output terminals U/T1, V/T2 and W/T3 when the length of each wire does not exceed
30m. If there is a need to bring the inverter into UL compliance, use wires specified in chapter 9.
with a maximum allowable temperature of 75°C) used at an ambient temperature of 50°C or less.
2
)
Note 4)
Grounding cable
IEC
For Japan
Compliant
*1
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
4.0
3.5
10
5.5
16
5.5
16
8.0
16
8.0
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
4.0
3.5
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
4.0
3.5
6.0
3.5
10
5.5
16
5.5
2
or more in diameter.
J-2