Installation Of An Overload Relay - Toshiba Tosvert VF-S15 Instruction Manual

Industrial inverter (for 3-phase induction motors)
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

 Magnetic contactor in the secondary circuit
A magnetic contactor may be installed on the secondary side to switch controlled motors or supply
commercial power to the load when the inverter is out of operation.
Notes on wiring
 Be sure to interlock the magnetic contactor on the secondary side with the power supply to prevent commercial
power from being applied to the inverter output terminals.
 When installing a magnetic contactor (MC) between the inverter and the motor, avoid turning the magnetic
contactor on or off during operation. Turning the magnetic contactor on or off during operation causes a current
to rush into the inverter which could lead to malfunction.

10.3 Installation of an overload relay

1)
This inverter has an electronic-thermal overload protective function.
In the following cases, however, an overload relay suitable for the adjustment of the motor electronic
thermal protection level (  ) and appropriate to the motor used should be installed between the inverter
and the motor.
 When using a motor with a current rating different to that of the corresponding Toshiba general-purpose
motor
 When operating a single motor with an output smaller than that of the applicable standard motor or more
than one motor simultaneously.
2)
When using this inverter to operate a constant-torque motor, such as the Toshiba VF motor, adjust the
protection characteristic of the electronic thermal protection unit ( 0m ) to the VF motor use.
3)
It is recommended to use a motor with a thermal relay embedded in the motor coil to give sufficient
protection to the motor, especially when it runs in a low-speed range.
J-5
E6581926
10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents