Toshiba Tosvert VF-S15 Instruction Manual page 33

Industrial inverter (for 3-phase induction motors)
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

3) Control circuit terminal block
The control circuit terminal block is common to all equipment.
SW2
VIA
VIB CC VIC S3 FM
PP
R CC +SU STO
CC
OUT P24 F
NO
1.3.3(3)_制御回路端子台_J.eps
Screw size
M3 screw
Refer to section 2.3.2 for details about all terminal functions.
Wire size
Conductor
Solid
Stranded
Recommended ferrule
Using ferrule to be improved efficiency and reliability of wiring is recommended.
Wire size
2
mm
(AWG)
0.34 (22)
0.5 (20)
0.75 (18)
1 (18)
1.5 (16)
*2
2 X 0.5 (-)
*2
2 X0.75 (-)
*1: Crimping pliers
CRIMPFOX ZA3 (PHOENIX CONTACT)
CT1 (Dinkle International., Ltd)
*2: These ferrules enable practical crimping of two wires in a ferrule.
SW1
FLA FLB FLC RY RC
Screw for removable control terminal block
RES S1 S2
Recommended
tightening torque
0.5 N  m
4.4 lb  in
1 wire
2
0.3-1.5mm
(AWG 22-16)
PHOENIX CONTACT
AI 0.34-6TQ
AI 0.5-6WH
AI 0.75-6GY
AI 1-6RD
AI 1.5-8BK
AI TWIN2 X 0.5-8WH
AI TWIN2 X 0.75-8GY
A-21
SW2
VIB
S4
PTC
S3
RS485 connector
Stripping length: 6 (mm)
Screwdriver: Small-sized flat-blade screwdriver
(Blade thickness: 0.5 mm, blade width: 3.5 mm)
2 wires of same size
2
0.3-0.75mm
(AWG 22-18)
Type
Dinkle International.,Ltd
DN00306
DN00506
DN00706
DN01006
DN01508
DTE00508
DTE00708
E6581926
SW1
SINK SOURCE
1
PLC

Hide quick links: