7) Operating a permanent magnet motor
Setting of V/F control mode selection to (PM motor control)
Permanent magnet motors (PM motors) that are light, small in size and highly efficient, as compared to
induction motors, can be operated in sensor-less operation mode.
Note that this feature can be used only for specific motors. For more information, contact your Toshiba
distributor.
8) Setting of V/f characteristic arbitrarily
Setting of V/f control mode selection pt to 7 (V/f 5-point setting)
In this mode, the base frequency and the base frequency voltage for the V/f control need to be set to operate
the motor while switching a maximum of 5 different V/f characteristics.
[Parameter setting]
Title
6
* 100% value is 200V for 200V class, and 400V for 400V class.
[V]/[%]
Note 1: Restrict the value of torque to boost (vb) to 3% or so. Boosting the torque too much may impair the
linearity between points.
Note 2: Please note if the inclination of each V/f is too high (exceeding 8.25%/Hz), a-02 (Points setting alarm 2)
will occur.
Function
V/f 5-point setting VF1 frequency
V/f 5-point setting VF1 voltage
V/f 5-point setting VF2 frequency
V/f 5-point setting VF2 voltage
V/f 5-point setting VF3 frequency
V/f 5-point setting VF3 voltage
V/f 5-point setting VF4 frequency
V/f 5-point setting VF4 voltage
V/f 5-point setting VF5 frequency
V/f 5-point setting VF5 voltage
Base frequency
voltage 1
VF1
0
Adjustment range
~ (Hz)
~ (%) / (V) *
~ (Hz)
~ (%) / (V) *
~ (Hz)
~ (%) / (V) *
~ Hz
~ (%) / (V) *
~ (Hz)
~ (%) / (V) *
V/f 5-point setting
VF5
VF4
VF3
VF2
F-22
E6581926
Default setting
Output frequency [Hz]
Base frequency 1