[Parameter setting]
Title
Function
Dynamic braking selection
f304
f305
Overvoltage limit operation
Dynamic braking resistance
f308
f309
Dynamic braking resistor capacity
f626 Over-voltage stall protection level
● To use this inverter in applications that create a continuously regenerative status (such as downward
movement of a lift, a press or a tension control machine), or in applications that require deceleration
stopping of a machine with a significant load inertial moment, increase the dynamic braking resistor
capacity according to the operation rate required.
● To connect an external dynamic braking resistor, select one with a resultant resistance value greater than
the minimum allowable resistance value. Be sure to set the appropriate operation rate in f308 and
f309 to ensure overload protection.
● When using a braking resistor with no thermal fuse, connect and use a thermal relay as a control circuit for
cutting the power off.
Setting
1
1
Proper value
Proper value
136 (%) (200V class)
141 (%) (400V class)
F-67
E6581926
6