(Continued)
Error code
In forced operation
STO signal OFF
/
/
Note 2)
Note 2) is blinking when setup menu starts. Key operation is not allowed.
[Prealarm display]
13
If two or more problems arise simultaneously, one of the following alarms appears and blinks.
, ,
The blinking alarms , , , h, t are displayed in this order from left to right.
Problem
Output frequency
An attempt was made to operate at a
upper limit
frequency higher than 10 times the base
frequency ( or ).
Operation panel key
The RUN or STOP key is held down for
alarm
more than 20 seconds.
The RUN or STOP key is faulty.
S3 terminal alarm
Slide switch SW2 and parameter f147
settings are different.
Auto-tuning in process
Auto-tuning
Break in analog
The signal input via VIC is below the
signal cable
analog signal detection level set with
and setting value of is
one or more.
"" and operation frequency is
displayed alternately in operation of
forced fire-speed control.
STO terminal is in open-circuit.
Input voltage of STO terminal is low.
Password verification
After the password setting (f738), the
result
password was input to f739 (password
verification).
The EASY key was pushed in the
Switching display of
Easy setting mode /
standard monitor mode.
Standard setting
mode
Input requirement of
Set the region setting parameter set to
region setting
default setting by selecting set=0. A
region setting is not input yet.
No trip of past trip
No new record of past trip, after past trips
were clear.
No detailed
The detailed information of past trip is
information of past
read by pushing the center of setting dial
trip
during blinking nerr ⇔ number.
But parameter set doesn't blink as same as other parameters.
Overcurrent alarm
Same as (overcurrent)
Overvoltage alarm
Same as (overvoltage)
Overload alarm
Same as and (overload)
Overheat alarm
Same as (overheat)
Communication alarm
Same as err5 (communication fault)
Possible causes
Operate at a frequency within 10 times the
base frequency.
Check the operation panel.
Match the settings of SW2 and f147.
Power supply OFF and ON after these
settings.
Normal if it the message disappears after a
few seconds.
Check the cables for breaks. And check the
setting of input signal or setting value of
and .
It is normal the alarm is gone out after the
forced fire-speed control operation.
Close STO and + SU circuit.
Check the load of P24 terminal, if STO and
+SU is shorted.
If the password is correct, pass is displayed
and if it is incorrect, fail is displayed.
When easy is displayed, setting mode
becomes easy setting mode. When std is
displayed, it becomes standard setting mode.
Normal operation.
Normal operation.
To be returned by pressing MODE key.
M-6
Remedies
Set a region setting by using setting dial.
Refer to section 4.4.