6.34.8 Cancel the operation command
f719 : Selection of operation command clear
 Function
This parameter allows you to select operation command retained or operation command cleared, when
coast stop occurs due to standby terminal function (ST), coast stop command terminal function (FRR),
control terminal opened between STO and +SU, and when under voltage in main circuit alarm( moff )
occurs, during panel operation or RS485 communication operation.
Parameter
setting
Operation command
=
=
=
=
Operation command retained :
Inverter restarts due to clearing coast stop at coast stop.
Inverter restarts due to supply power source again when the under voltage in main circuit alarm ()
occurs.
Operation command cleared :
Inverter doesn't restart after coast stop or occurring the under voltage in main circuit alarm ().
Press RUN key to operate again in panel operation.
Switch to ON the operation command in RS485 communication operation.
Title
Selection of operation
f719
command clear
[Setup example of input terminal]
When it is assigned to the RES terminal.
Title
Input terminal selection 3A
f113 
(RES)
Input terminal selection 3A
f113 
(RES)
Setting value 7, 97 are reverse signal.
At coast stop
in main circuit alarm ( moff )
cleared
Operation command retained
Operation command cleared
Operation command cleared
Function
0: Clear at coast stop and retained at
moff .
1: Retained at coast stop and moff .
2: Clear at coast stop and moff .
3: 2+ clear when cmod is changed
Function
Adjustment range
0-203
0-203
F-129
At under voltage
Operation command retained
Adjustment range
Setting
6: ST (Standby)
96: FRR (Coast stop command)
E6581926
comd
is changed
Operation command
retained
6
Default setting
1