Toshiba Tosvert VF-S15 Instruction Manual page 141

Industrial inverter (for 3-phase induction motors)
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

6.6.3
f109 : Analog/logic input selection (VIA/VIB)
 Function
[Parameter setting]
Title
f109
Note) When using VIA terminal as contact input terminals, be sure to insert a resistor between P24 terminal
6
Changing the functions of VIA and VIB terminals
This parameter allows you to choose between analog signal input and contact signal input for the VIA
and VIB terminals.
Function
Analog/logic input
selection
(VIA/VIB)
and VIA terminal in sink logic connection, and insert a resistor between VIA terminal and CC terminal in
source logic connection. (Recommended resistance: 4.7k-1/2W)
When using VIB terminal as contact input terminals, set the upper side of slide switch SW2 to S4 side
and then set f109.
Adjustment range
0: VIA - analog input
VIB - analog input
1: VIA - analog input
VIB - contact input
2: -
3: VIA - contact input (Sink)
VIB - contact input
4: VIA - contact input (Source)
VIB - contact input
F-30
E6581926
Default setting
0