Toshiba Tosvert VF-S15 Instruction Manual page 198

Industrial inverter (for 3-phase induction motors)
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

6.25.2 Setting motor constants for PM motors
f400 : Auto-tuning
f402 : Automatic torque boost value
f405 : Motor rated capacity
f415 : Motor rated current
f417 : Motor rated speed
f459 : Load inertia moment ratio
Caution:
If the settings for V/F control mode selections pt is 6: vector control for PM motor
Look at the motor's name plate and set the following parameters.
vl: Base frequency 1 (rated frequency) that is calculated from Back EMF
vlv: Base frequency voltage 1 (rated voltage) that is calculated from Back EMF
f405: Motor rated capacity
6
f415: Motor rated current
f417: Motor rated speed
f912: Q axis inductance per phase
f913: D axis inductance per phase
[Selection 1: Setting PM motor control and auto-tuning]
After setting pt =6, auto-tuning occurs.
Set the auto-tuning parameter f400 to 2 (Auto-tuning enabled)
[Parameter setting]
Title
f400
Note1) When parameter pt= 6 is selected, f400=3 to 5 do not work.
Function
0: Auto-tuning disabled
1: Initialization of f402, f912, f913
(after execution : 0)
2: Auto-tuning executed
Auto-tuning
(after execution: 0)
3: -
4: -
5: -
F-86
f462 : Speed reference filter
coefficient
f912 : q-axis inductance
f913 : d-axis inductance
f915 : PM control mode selection
Adjustment range
E6581926
Default setting
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents