Toshiba Tosvert VF-S15 Instruction Manual page 364

Industrial inverter (for 3-phase induction motors)
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

Terminal
Input /
symbol
output
Shorting across F-CC or P24-F causes forward rotation; open
causes deceleration stop.
F
Input
(When Standby ST is always ON)
3 different functions can be assigned.
Shorting across R-CC or P24-R causes reverse rotation; open
causes deceleration stop.
R
Input
(When Standby ST is always ON)
3 different functions can be assigned.
This inverter protective function is reset if RES-CC or P24-RES is
connected. Shorting RES-CC or P24-RES has no effect when the
RES
Input
inverter is in a normal condition.
2 different functions can be assigned.
Shorting across S1-CC or P24-S1 causes preset speed operation.
S1
Input
2 different functions can be assigned.
Shorting across S2-CC or P24-S2 causes preset speed operation.
S2
Input
By changing parameter f146 setting, this terminal can also be
used as a pulse train input terminal.
Shorting across S3-CC or P24-S3 causes preset speed operation.
By changing slide switch SW2 and parameter f147 setting, this
S3
Input
terminal can also be used as a PTC input terminal.
Common
CC
to Input /
Control circuit's equipotential terminal (3 terminals)
output
PP
Output
Analog power supply output
Multifunction programmable analog input.
Default setting: 0-10Vdc (1/1000 resolution) and 0-60Hz (0-50Hz)
V I A
frequency input.
Input
Note 1)
By changing parameter f109, this terminal can also be used as a
multifunction programmable logic input terminal.
Multifunction programmable analog input.
Default setting: 0-10Vdc (1/1000 resolution) and 0-60Hz (0-50Hz)
frequency input.
V I B
The function can be changed to -10-+10V input (1/2000 resolution) by
Input
parameter f107 =1 setting.
Note 1)
By switching slide switch SW2 and changing parameter f109 setting,
this terminal can also be used as a multifunction programmable logic
input terminal.
Multifunction programmable analog input.
V I C
Input
4-20mA (0-20mA) input.
Function
Q-8
E6581926
Electrical
specifications
No voltage
logic input
24Vdc-5mA or
less
Sink/Source and
PLC selectable
using slide switch
SW1
(Default setting is
Sink side)
Pulse train input
(S2 terminal)
Pulse frequency
range:
10pps~2kpps
Duty: 50±10%
PTC input
(S3 terminal)
-
10Vdc
(permissible load
current: 10mAdc)
10Vdc
(internal
impedance: 30k)
10Vdc
(internal
impedance: 30k)
4-20mA
(internal
impedance: 250)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents