Toshiba Tosvert VF-S15 Instruction Manual page 337

Industrial inverter (for 3-phase induction motors)
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

<Continued>
Item
Protective function
Stall prevention, current limitation, over-current, output short circuit, over-voltage, over-voltage limitation,
undervoltage, ground fault detection, input phase failure, output phase failure, overload protection by electronic
thermal function, armature over-current at start-up, load side over-current at start-up, over-torque, undercurrent,
overheating, cumulative operation time, life alarm, emergency stop, braking resistor overcurrent / overload,
various pre-alarms
Electronic thermal
Switching between standard motor and constant-torque VF motor, switching between motors 1 & 2, setting of
characteristic
overload trip time, adjustment of stall prevention levels 1 & 2, selection of overload stall
Reset function
Panel reset / External signal reset / Power supply reset. This function is also used to save and clear trip records.
Alarms
Overcurrent, overvoltage, overload, overheat, communication error, under-voltage, setting error, retry in process,
upper/lower limits
Causes of failures
Overcurrent, overvoltage, overheat, output short-circuit, ground fault, overload on inverter, arm overcurrent at start-
up, overcurrent on the load side at start-up, CPU fault, EEPROM fault, RAM fault, ROM fault, communication error.
(Selectable: dynamic braking resistor overload, emergency stop, under-voltage, small current, over-torque, low-
torque, motor overload, input phase failure, output phase failure)
Monitoring function
Output frequency, frequency command value, operation frequency command, forward/reverse run, output current,
input voltage (DC detection), output voltage, torque, inverter load factor, motor load factor, braking resistor load
factor, input power, output power, information on input terminals, information on output terminals, overload and
region setting, version of CPU1, version of CPU2, PID feedback value, stator frequency, causes of past trips 1to 8,
parts replacement alarm, cumulative operation time, number of starting
Past trip monitoring
Stores data on the past eight trips: number of trips that occurred in succession, output frequency, frequency
function
command value, forward/reverse run, output current, input voltage (DC detection), output voltage, information on
input terminals, information on output terminals, and cumulative operation time when each trip occurred.
Output for frequency
Analog output for meter:
meter
0 - 20mA (4 to 20mA) output: DC ammeter (allowable load resistance: 600Ω or less)
0 - 10V output:
Maximum resolution:
4-digit 7-segments LED
Frequency:
Alarm:
Status:
Free-unit display: arbitrary unit (e.g. rotating speed) corresponding to output frequency.
Lamps indicating the inverter status by lighting, such as RUN lamp, MON lamp, PRG lamp,  lamp, Hz lamp.
Indicator
The charge lamp indicates that the main circuit capacitors are electrically charged.
Safety function
Safe Torque Off (STO) function according to EN/IEC 61508 SIL2 and ISO 13849-1 category 3 PL"d".
Location of use
Indoors; not exposed to direct sunlight, corrosive gas, explosive gas, flammable gas, oil mist, or dust; and vibration
Elevation
3000 m or less (current reduction required over 1000 m) Note 3)
Ambient temperature
-10 to +60°C Note 4)
Storage temperature
-25 to +70°C
Relative humidity
5 to 95% (free from condensation and vapor).
Note 1. Maximum output voltage is the same as the input voltage.
Note 2. A chattering (momentary ON/OFF of contact) is generated by external factors of the vibration and the impact, etc. In
particular, please set the filter of 10ms or more, or timer for measures when connecting it directly with input unit
terminal of programmable controller. Please use the OUT terminal as much as possible when the programmable
controller is connected.
Note 3. Current must be reduced by 1% for each 100 m over 1000 m. For example, 90% at 2000m and 80% at 3000m.
Note 4. When using the inverter in locations with temperatures above 40°C, remove the protective label on the top of the
inverter and use the inverter with the output current reduced according to section 6.18.
.
To align the inverters side-by-side horizontally, remove the protective label on the top of the inverter before use. When
using the inverter in locations with temperatures above 40°C, use the inverter with the output current reduced.
1mA dc full-scale dc ammeter
DC voltmeter (allowable load resistance: 1kΩ or more)
1/1000
inverter output frequency.
overcurrent alarm "c", overvoltage alarm "p", overload alarm "l", overheat alarm "h",
communication alarm "t".
inverter status (frequency, cause of activation of protective function, input/output voltage, output
current, etc.) and parameter settings.
2
of less than 5.9m/s
(10 to 55Hz).
L-3