Toshiba Tosvert VF-S15 Instruction Manual page 344

Industrial inverter (for 3-phase induction motors)
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

(Continued)
Error code
Failure code
0028

0054

0055

0056

0022

*
002F

003B

0029

002D

*
0032

0033

0034

0035

0037
13

003A

0063

0040

0045

* This marking trips can be selected valid or invalid by parameters.
Problem
Auto-tuning error
 The motor parameter , , ,
,  are not set correctly.
 The motor with the capacity of 2 classes
or less than the inverter is used.
 The output cable is too thin.
 The inverter is used for loads other than
those of three-phase induction motors.
 The motor is not connected.
 The motor is rotating.
 Parameter pt=6 is set and High speed
motor is connected.
Ground fault
 A ground fault occurs in the output cable
or the motor.
 Overcurrent of dynamic braking resistor
 When inverters are fed by AC power
supply and connected with common DC
bus link, unnecessary trip occurs.
Step-out (for PM
 The motor shaft is locked.
motor drive only)
 One output phase is open.
 An impact load is applied.
 Using the DC braking function.
Safe torque off error
 Error of safe torque off circuit
Inverter type error
 It may be a breakdown failure.
Over speed fault
 The input voltage fluctuates abnormally.
 Over speed fault due to the overvoltage
limit operation.
Analog input break
 The input signal from VIC is equal to or
detection fault
less than the  setting.
 A communications error occurs between
CPU communications
error
control CPUs.
Over torque boost
 The automatic torque boost parameter
fault
 setting is too high.
 The motor has too small impedance.
 The control CPU is defective.
CPU fault 2
Optional unit fault 2
 An optional device is defective.
CPU fault 3
 The control CPU is defective.
Heavy cycle of main
 Main power ON/OFF during running is
power ON/OFF
repeated frequently.
 Internal failure if it is caused by other
reasons.
 PTC thermal protection is occurred.
PTC fault
Servo lock fault
 The motor shaft is not locked in servo lock
operation.
Possible causes
 Set the left column parameters correctly
 Set parameter f416 to smaller 70% of
 Set the left column parameters correctly
 Then set f400=1, when trip occurs.
 Connect the motor.
 Check whether the secondary magnetic
 Make an auto-tuning again after the
 Choose the higher power range drive.
 Check the cable and the motor for ground
 Increase the deceleration time dec.
 Set the supply voltage correction f307
 Set the parameter f614 to 0
 Unlock the motor shaft.
 Check the interconnect cables between
 Prolong the acceleration / deceleration
 Turn off the Step-out function when using
 Contact your Toshiba distributor.
 Contact your Toshiba distributor.
 Check the input voltage.
 Install an optional dynamic braking
 Check the VIC signal cable for breaks.
 Contact your Toshiba distributor.
 Set a lower automatic torque boost
 Make an auto-tuning.
 Contact your Toshiba distributor.
 Contact your Toshiba distributor.
 Contact your Toshiba distributor.
 Reduce the frequency of repetition of
 Contact your Toshiba distributor.
 Check the PTC in motor.
 Reduce the load in servo lock operation.
M-4
E6581926
Remedies
as a motor name plate and make an auto-
tuning again.
the present value, and execute the auto-
tuning again.
as a motor name plate and make an auto-
tuning again.
contactor.
rotation of the motor stops.
(1 class up drive is recommended.)
faults.
to 1 or 3.
"Disabled".
the inverter and the motor.
time.
the DC braking function or change the DC
braking to Servo lock function.
resistor. (optional)
Also, check the input signal value or
setting of .
parameter  setting.
main power ON/OFF during running.
(Continued overleaf)