Toshiba Tosvert VF-S15 Instruction Manual page 190

Industrial inverter (for 3-phase induction motors)
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

1)
External connection
(1) Process
value
DC: 0 to 10V
2) Selecting process value and feedback value
Process value (frequency) and feedback value can be combined as follows for the PID control.
(1) Process value
PID control reference signal selection f389
0: fmod/f207 selected
1: Terminal VIA
2: Terminal VIB
3: fpid
4: RS485 communication
5: UP/DOWN from external logic input
6: CANopen communication
7: Communication option
8: Terminal VIC
9, 10: -
11: Pulse train input
Note 1: When setting f389, do not select the same signal used for feedback input.
Note 2: When f389=3 is set, the process value is set by the parameter fpid.
fpid can be set by the setting dial in the standard monitor mode.
Please inactivate the frequency setting by the setting dial (fc, Preset-speed frequency)
(Set fmod/f207 other than 0 or 3, f660 other than 4, f724 to 0.)
Note 3: Signal is put out when the amount of feedback matches to the amount of processing.
Assign function number 144 or 145 to an output terminal.
Frequency agreement detection range (f167) can also be set.
R/L1
U/T1
S/L2
V/T2
T/L3
W/T3
VIA
CC
VIC
CC
(2)Feedback signals DC : 4~20mA
(2) Feedback value
PID control feedback signal selection 
0: Disabled
1: Terminal VIA
2: Terminal VIB
3: Terminal VIC
4 to 6: -
F-79
E6581926
M
Pressure
transmitter
P
6