Figure 3-15. Making Retimer Connections

Making Alarm Connections

To install alarm connections on the Input Module, use a customer-supplied DB-25
connector to build an alarm connection to the TimeProvider.
pinout for the DB-25 Alarm connector found on all the Input modules (except the
wire wrap version).
Table 3-6. Alarm Connector Pinout
Pin
1
2
3
4
5
6
7
8
9
097-58001-02 Revision C – August 2005
Description
No Connection
Minor Normally Closed (NC) Audible
Minor Common Audible
Minor NC Visual
Minor Common Visual
Major NC Audible
Major Common Audible
Major NC Visual
Major Common Visual
Chapter 3 Installing the TimeProvider
Making Connections
Table 3-6