Provisioning Alarms; Provisioning The Alarm Levels - Symmetricom TimeProvider 1000 User Manual

Edge clock
Hide thumbs Also See for TimeProvider 1000:
Table of Contents

Advertisement

Chapter 4 Provisioning the TimeProvider

Provisioning Alarms

Provisioning Alarms
This section describes how you provision and manage alarms in the TimeProvider.
There are TL1 commands that allow you to:
Provision individual alarm levels
Provision system-wide alarm levels
Display current alarm settings
Display current alarms
Display alarm status
Alarms are displayed on the IMC LEDs; they also appear on the relay contact
closures on the Input module.

Provisioning the Alarm Levels

Use the SET-ATTR command to set the alarms associated with the IMC and IOC.
You can use this command to reset all alarm levels to the factory default values, and
to allow the TimeProvider to escalate alarms.
SET-ATTR:[<tid>]:<aid>:[<ctag>]::<keyword>[=<value>];
This command has a default access level of ADMIN.
<aid>
<keyword>
SYS
ELEVTIME
FACTORY
<aid>
<keyword>
SYS
Alarm ID
IMC
IOC
PRS
INPp (p = 1 | 2)
114 TimeProvider User's Guide
<value>
ENABLE | DISABLE (default)
<value>
NR = Not Reported
NA = A non-alarm event
MN = Minor alarm
MJ = Major alarm
CR = Critical alarm
CLEAR = Clears an active
alarm; if the condition persists,
then the alarm is reissued
Description
System level
Allow alarms to escalate from
Minor to Major and from
Major to Critical
Set the alarm levels to factory
default values
Description
See the definitions for the
Alarm ID in the following table
097-58001-02 Revision C – August 2005