Use only shielded cable for all signal wiring, including I/O, clocks and Ethernet,
and ground appropriately at both ends, or as required by local standards.
Secure all cable screws to their corresponding connectors.
Caution: To avoid interference to the TimeProvider, you must
consider the electromagnetic compatibility (EMC) of nearby
equipment when preparing to install the TimeProvider.
Electromagnetic interference can adversely affect the operation
of nearby equipment.
Gathering the Tools
These standard tools and materials are not supplied, but may be required for
installing the TimeProvider:
Standard tool kit
Cable ties, waxed string or acceptable cable clamps
No. 16 AWG (minimum) wire (1.31 mm
Ground
Telecom signal wiring (including I/O, clock, and Ethernet) uses shielded cabling
of the appropriate impedance required by the specific signal type
Mating connectors for terminating signal wiring
For wire wrap connections only: No. 22 AWG (0.326 mm
wire-wrap cable of the appropriate impedance for the specific signal
requirements
Wire wrap tool (wire wrap modules only)
Fasteners for mounting the equipment in rack
Digital Voltmeter (DVM)
Soldering iron and solder for the ETSI-version power connectors
097-58001-02 Revision C – August 2005
Chapter 3 Installing the TimeProvider
2
) for –48 V DC, return, and Frame
2
) shielded twisted pair
TimeProvider User's Guide
Getting Started
49