Autonomous Message
A 1179 REPT EVT
CHANGED,AUTO\""
;
To manually set the location of the receiver, you must enter the latitude, the
longitude, and the altitude (in m) in the same command, using commas to separate
the parameters.
Sample Command
ED-EQPT::GPS:TS1000::POS=30-28-34.0N,97-50-16.0W,333.0;
Autonomous Message
A 1179 REPT EVT
HAS CHANGED,MANUAL\""
;

Setting the Input Frequency

Use the ED-SYNC command to provision the input PRS frequency.
ED-SYNC:[<tid>]:<aid>:[<ctag>]::<keyword>=<value>;
This command has a default access level of ADMIN.
<aid>
<keyword>
PRS
FRMTYPE
Sample Command
ED-SYNC::PRS:TS1000::FRMTYPE=5M;
Autonomous Message
A 1179 REPT EVT
FRAMING TYPE HAS CHANGED,5M\""
;
097-58001-02 Revision C – August 2005
TP-SSU 03-10-24 10:45:15
"GPS,EQPT:NA,FRMTYPE,NSA,03-10-24 10-45-15:\"GPS MODE HAS
TP-SSU 03-10-24 10:45:15
"GPS,EQPT:NA,FRMTYPE,NSA,03-10-24 10-45-15:\"GPS LOCATION
<value>
1.544 M | 2M
(2.048 MHz) | 5M
| 6.312 M | 10M
TP-SSU 03-10-24 10:46:01
"PRS,EQPT:NA,FRMTYPE,NSA,03-10-24 10-46-01:\"INPUT
Chapter 4 Provisioning the TimeProvider
Provisioning the Input Reference
Description
PRS input provisioning
Provisions the input
frequency of the PRS
input
TimeProvider User's Guide 101
Default value
2M