Clearing Alarms - Symmetricom TimeProvider 1000 User Manual

Edge clock
Hide thumbs Also See for TimeProvider 1000:
Table of Contents

Advertisement

Response
<aid>
OUTg
g = 1 | 2 | 3 | 4
RTMg
g = 1 | 2 | 3 | 4
Sample Command
RTRV-COND::IOC:TS1000;
This command causes the TimeProvider to return the status of the power supplies
and the optional Expansion Panel.
Normal Response
M
;

Clearing Alarms

Clearing the Office (Audible) Alarm
Use the following TL1 command to turn off (squelch) the audible office alarm. The
office alarm reactivates when a new alarm occurs.
OPR-ACO-ALL:[<tid>]::[<ctag>];
This command has a default access level of USER.
Sample Command
OPR-ACO-ALL:::TS1000;
Normal Response
M
DEACTIVATED"
;
097-58001-02 Revision C – August 2005
Displays output status; this reflects the state of IOCFAIL of the active
IOC. Unequipped indicates OUTgEQPT module removed.
<outstatus> – OK | ALM | UNEQUIPPED
Displays Retimer status and any alarm events associated with both
ports 1 and 2 on the specified Retimer module. Unequipped
indicated RTMgEQPT module removed
<rtm1status> – OK | ALM | UNEQUIPPED
<rtm2status> – OK | ALM | UNEQUIPPED
TP-SSU 03-10-24 11:27:28
TS1000 COMPLD
"SYS,PWRA-OK,PWRB-OK,OK,OK"
TP-SSU 03-10-24 11:26:47
TS1000 COMPLD
"IMC,EQPT:NA,ACO,NSA,03-10-24 11-26-47:\"AUDIO ALARM IS
Chapter 4 Provisioning the TimeProvider
Description
TimeProvider User's Guide 127