Mitsubishi MR-JE-10A Instruction Manual page 279

Servo amplifiers
Table of Contents

Advertisement

11. OPTIONS AND PERIPHERAL EQUIPMENT
(2) Noise reduction techniques
(a) Data line filter (recommended)
Noise can be prevented by installing a data line filter onto the encoder cable, etc.
For example, ZCAT3035-1330 by TDK, ESD-SR-250 by NEC TOKIN, GRFC-13 by Kitagawa
Industries, and E04SRM563218 by SEIWA ELECTRIC are available as data line filters.
As a reference example, the impedance specifications of the ZCAT3035-1330 (TDK) are indicated
below. This impedances are reference values and not guaranteed values.
(b) Surge killer (recommended)
Use of a surge killer is recommended for AC relay, magnetic contactor or the like near the servo
amplifier. Use the following surge killer or equivalent.
Rated
C
R
voltage
[µF ± 20%]
[Ω ± 30%]
AC [V]
50
250
0.5
(1/2 W)
Note that a diode should be installed to a DC relay or the like.
Maximum voltage: not less than four times the drive voltage of the relay or
Maximum current: not less than two times the drive current of the relay or
Impedance [Ω]
10 MHz to 100 MHz
80
OFF
ON
MC
Surge killer
(Ex.) CR-50500 Okaya Electric Industries)
Test voltage
Between terminals:
625 V AC, 50/60 Hz 60 s
Between terminal and case:
2000 V AC, 50/60 Hz 60 s
the like
the like
100 MHz to 500 MHz
150
Product name
MC
SK
Relay
This distance should be short
Dimensions [Unit: mm]
Band (clear)
AWG 18 Twisted wire
15 ± 1
Soldered
CR-50500
6 ± 1
300 min.
48 ± 1.5
11 - 24
39 ± 1
Loop for fixing the
34 ± 1
cable band
TDK
Lot number
Outline drawing (ZCAT3035-1330)
Surge killer
(within 20 cm).
6 ± 1
300 min.
16 ± 1
+
Diode
[Unit: mm]
φ3.6
(18.5 + 5) max.
-
RA

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents