7. SPECIAL ADJUSTMENT FUNCTIONS

7.1.3 Shaft resonance suppression filter

(1) Function
When a load is mounted to the servo motor shaft, resonance by shaft torsion during driving may
generate a mechanical vibration at high frequency. The shaft resonance suppression filter suppresses
the vibration.
When you select "Automatic setting", the filter will be set automatically on the basis of the servo motor
you use and the load to motor inertia ratio. The disabled setting increases the response of the servo
amplifier for high resonance frequency.
(2) Parameter
Set "Shaft resonance suppression filter selection" in [Pr. PB23].
To set [Pr. PB17 Shaft resonance suppression filter] automatically, select "Automatic setting".
To set [Pr. PB17 Shaft resonance suppression filter] manually, select "Manual setting". The setting
values are as follows.
POINT
This filter is set properly by default according to servo motor you use and load
moment of inertia. For [Pr. PB23], "_ _ _ 0" (automatic setting) is recommended
because setting "Shaft resonance suppression filter selection" in [Pr. PB23] or
setting [Pr. PB17 Shaft resonance suppression filter] can degrades in
performance.
[Pr. PB23]
0 1 0
Shaft resonance suppression filter setting frequency selection
Setting value
Frequency [Hz]
_ _ 0 0
_ _ 0 1
_ _ 0 2
_ _ 0 3
_ _ 0 4
_ _ 0 5
_ _ 0 6
_ _ 0 7
_ _ 0 8
_ _ 0 9
_ _ 0 A
_ _ 0 B
_ _ 0 C
_ _ 0 D
_ _ 0 E
_ _ 0 F
Shaft resonance suppression filter selection
0: Automatic setting
1: Manual setting
2: Disabled
Setting value
Disabled
_ _ 1 0
Disabled
_ _ 1 1
4500
_ _ 1 2
3000
_ _ 1 3
2250
_ _ 1 4
1800
_ _ 1 5
1500
_ _ 1 6
1285
_ _ 1 7
1125
_ _ 1 8
1000
_ _ 1 9
900
_ _ 1 A
818
_ _ 1 B
750
_ _ 1 C
692
_ _ 1 D
642
_ _ 1 E
600
_ _ 1 F
7 - 6
Frequency [Hz]
562
529
500
473
450
428
409
391
375
360
346
333
321
310
300
290