External 24 VDC power supply
A 24 VDC power supply is needed to supply the V90 PN servo drive. Refer to the table
below to select the power supply:
Without a holding brake
Rated voltage (V)
24 (-15% to +20%)
The minimum voltage of 24 VDC -10% must be available at the connector on the motor side in
1)
order to guarantee that the brake reliably opens. If the maximum voltage of 24 VDC +10% is ex-
ceeded, then the brake could re-close. The voltage drop along the brake feeder cable must be
taken into consideration. The voltage drop ΔU for copper cables can be approximately calculated
as follows:
ΔU [V] = 0.042 Ω·mm
Where: l = Cable length [m], q = Brake cable cross section [mm
Fuse/Type-E combination motor controller
A fuse/type-E combination motor controller/circuit breaker can be used to protect the system.
Integral solid state short circuit protection does not provide branch circuit protection. Branch
circuit protection must be provided in accordance with the National Electrical Code and any
additional local codes. Refer to the table below for the selection of fuses, type-E combination
motor controllers, and circuit breakers:
SINAMICS V90 PN 200 V variant
SINAMICS V90 PN
Power
Frame
supply
size
1-phase,
FSB
200 VAC to
240 VAC
FSC
3-phase,
FSB
200 VAC to
240 VAC
FSC
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 04/2017, A5E37208830-003
Maximum current (A)
1.5
/m ∙ (l/q) ∙ I
2
Recommended fuse
Rated
CE-
UL/cUL-compliant
power
compliant
listed (JDDZ) fuse
(kW)
0.1
3NA3 801
6 A
(6 A)
0.2
3NA3 801
6 A
(6 A)
0.4
3NA3 803
10 A
(10 A)
0.75
3NA3 805
20 A
(16 A)
0.1
3NA3 801
6 A
(6 A)
0.2
3NA3 801
6 A
(6 A)
0.4
3NA3 803
10 A
(10 A)
0.75
3NA3 805
20 A
(16 A)
With a holding brake
Rated voltage (V)
24 (-10% to +10%)
Brake
Type-E combination motor controller
Rated
current
(A)
2.8 to 4
2.8 to 4
5.5 to 8
9 to 12.5
2.8 to 4
2.8 to 4
2.8 to 4
5.5 to 8
General information
Maximum current (A)
1.5 + motor holding
1)
brake rated current
], I
= DC current of brake [A]
2
Brake
1)
Rated volt-
Rated
age (VAC)
power
(hp)
230/240
1/3
230/240
1/3
230/240
1
230/240
2
230/240
3/4
230/240
3/4
230/240
3/4
230/240
2
2.4 Accessories
Article number
3RV 2011-
1EA10
3RV 2011-
1EA10
3RV 2011-
1HA10
3RV 2011-
1KA10
3RV 2011-
1EA10
3RV 2011-
1EA10
3RV 2011-
1EA10
3RV 2011-
1HA10
41