Wiring
The digital inputs support both PNP and NPN types of wirings. You can find detailed
information from the following diagrams:
4.3.1.2
DOs
You can assign a maximum of 10 internal digital output signals to the SINAMICS V90 PN
servo drive. For detailed information about these signals, see the table below:
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 04/2017, A5E37208830-003
NPN wiring
Name
RDY
Servo ready
1: the drive is ready.
•
0: the drive is not ready (a fault occurs or the enable signal is missing).
•
FAULT
Fault
1: in the fault state.
•
0: no fault.
•
ZSP
Zero speed detection
1: motor speed ≤ zero speed (can be set with parameter p2161).
•
0: motor speed > zero speed + hysteresis (10 rpm).
•
TLR
Torque limit reached
1: the generated torque has nearly (internal hysteresis) reached the value of
•
the positive torque limit or negative torque limit.
0: the generated torque has not reached any torque limit.
•
MBR
Motor holding brake
1: the motor holding brake is engaged.
•
0: the motor holding brake is released.
•
Note: MBR is only a status signal because the control and the power supply of
the motor holding brake are realized with separate terminals.
4.3 Control/status interface - X8
PNP wiring
Descriptions
Connecting
101