Alarm
A8511: PROFIdrive: Receive
configuration data invalid
Message class: Error in the
parameteriza-
tion/configuration/commission
ing procedure (18)
A8526: PROFIdrive: No cyclic
connection
Message class: Communica-
tion to the higher-level con-
troller faulted (9)
A8565: PROFIdrive: Receive
configuration data invalid
Message class: Error in the
parameteriza-
tion/configuration/commission
ing procedure (18)
A30016: Load supply
switched off
Message class: Network fault
(2)
A30031: Hardware current
limiting in phase U
Message class: Power elec-
tronics faulted (5)
A31411: Encoder 1: Absolute
encoder signals internal
alarms
Message class: Actual posi-
tion/speed value incorrect or
not available (11)
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 04/2017, A5E37208830-003
Cause
The drive unit did not accept the receive
configuration data.
There is no cyclic connection to the con-
trol.
A consistency error was detected when
activating the configuration.
Note: Currently set configuration has not
been activated.
The DC link voltage is too low.
Hardware current limit for phase U re-
sponded. The pulsing in this phase is in-
hibited for one pulse period.
Closed-loop control is incorrectly pa-
rameterized.
Fault in the motor or in the power ca-
bles.
The power cables exceed the maxi-
mum permissible length.
Motor load too high.
Power unit defective.
Note:
Alarm A30031 is always output if, for a
power unit, the hardware current limiting of
phase U, V or W responds.
The absolute encoder fault word includes
alarm bits that have been set.
12.1 List of faults and alarms
Remedy
Check the receive configuration data.
Establish the cyclic connection and acti-
vate the control with cyclic operation.
Check the parameters "Name of Station"
and "IP of Station" (r8930, r8931).
Check the required interface configuration,
correct if necessary.
Switch on the load supply.
Check the line supply if necessary.
Check the motor data. As an alternative, run
a motor data identification.
Check the motor circuit configuration
(star-delta)
Check the motor load.
Check the power cable connections.
Check the power cables for short-circuit or
ground fault.
Check the length of the power cables.
Check the encoder cable connection and
make sure the cables are routed in com-
pliance with EMC.
Check the motor temperature.
Replace the motor/encoder.
Diagnostics