Diagnostics
12.1 List of faults and alarms
Alarm
A31412: Error bit set in the
serial protocol
Message class: Actual posi-
tion/speed value incorrect or
not available (11)
A52900: Failure during data
copying
Message class: General drive
fault (19)
A52901: Braking resistor
reaches alarm threshold
Message class: General drive
fault (19)
A52902: Emergency missing
Message class: General drive
fault (19)
300
Cause
The encoder sends a set error bit via the
serial protocol.
Copying is halted.
The micro SD card/SD card was
plugged out.
The drive is not in the stop state.
The heat capacity reaches the threshold
(p29005) of the braking resistor capacity.
Implement servo on when the emergency
input (EMGS) is switched off.
Remedy
Carry out a POWER ON (power off/on) for
all components.
Check that the cables are routed in com-
pliance with EMC.
Check the plug connections.
Replace the encoder.
Re-plug in the micro SD card/SD card.
Make sure the drive is in the stop state.
Change the external braking resistor.
Increase deceleration time.
Switch on the emergency input (EMGS) and
then implement servo on.
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 04/2017, A5E37208830-003